Wet Pipe Fire Sprinkler System

Image
Wet Pipe Fire Sprinkler System Wet pipe sprinkler systems are the simplest and most common fire suppression method on the market today. This fire sprinkler system is cost efficient and low maintenance. They are comprised of pipes that constantly contain pressurized water. When a sprinkler activates this water is immediately discharged onto the fire.  The first automatic, closed-type sprinkler head immediately discharges water, as more individual sprinkler heads are subsequently activated by heat, they too will discharge water onto the fire until it is controlled or extinguished. Wet pipe fire sprinkler systems can be installed in buildings not susceptible to freezing (i.e., where temperatures are above 40 degrees Fahrenheit).   Typically, a Fire Sprinkler Systems are made up from a series of components including; Stop Valve, Alarm Valve, Fire Sprinkler (head), Alarm Test Valve and Motorized Alarm Bell (Gong). In addition to this there are additional components ...

NFPA 13 PRESSURE TEST PROCEDURES

NFPA 13 PRESSURE TEST PROCEDURES  (Aboveground Fire Systems): A hydrostatic test is a pressure test to reveal the presence of leaks in the piping system. For fire protection systems, the piping is pressurized to 200 psi (13.8 bar) for a period of 2 hours.  During this time period, the system piping is inspected for leaks.  Leaks in the piping system are revealed either by observation of water droplets or by a reduction in test pressure. Any leaks or reduction in test pressure necessitates a repair of the pipe joint involved and a retest to verify that the leak has been repaired. In cases where high pressure exists, the standard requires that the test pressure be 50 psi (3.5 bar) in excess of the normal system pressure if the resultant test pressure will be greater than 200 psi (13.8 bar).. By NFPA: Unless permitted by 24.2.1.2 through 24.2.1.8, all piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested ...
Image
Bienvenidos.... Hablemos de Ingenieria.....